I will say, I've had an old mechanical window AC trip the ZEN15's overload detection when the thermostat short cycled and the compressor was stalled. So I would trust it for that in a pinch, and especially with a resistive load. But for an outdoor heating element application, I still would oversize the switching device (and get the 40A contactor), and put 15A circuit breakers before the contactor. Also, that 40A device can drive either a two pole 240V device (unison contacts) or two 120V devices, so you could just put each heater on its own pole and heat up your wiring a little less. Or probably just wire only one pole, I haven't read the manual.